{0;0;0;0} 0. Current document units is in Meters 1. Conversion to Meters will be applied = 1.000 2. Current working directory is set to: C:\Users\ASUS\AppData\Roaming\Ladybug\unnamed\OpenStudio 3. Can't find ddy file next to the EPW. 4. Extreme values from the weather file design will be used instead. 5. Model saved to: C:\Users\ASUS\AppData\Roaming\Ladybug\unnamed\OpenStudio\unnamed.osm 6. OSM > IDF: C:/Users/ASUS/AppData/Roaming/Ladybug/unnamed/OpenStudio/unnamed/ModelToIdf/in.idf 7. Program Version,EnergyPlus, Version 8.6.0-198c6a3cff, YMD=2018.05.11 02:41,IDD_Version 8.6.0 8. 9. ************* Beginning Zone Sizing Calculations 10. 11. ** Warning ** ProcessScheduleInput: Schedule:Constant="ALWAYS OFF DISCRETE", Blank Schedule Type Limits Name input -- will not be validated. 12. 13. ** Warning ** GetSurfaceData: InterZone Surface Areas do not match as expected and might not satisfy conservation of energy: 14. 15. ** ~~~ ** ...use Output:Diagnostics,DisplayExtraWarnings; to show more details on individual mismatches. 16. 17. ************* Beginning System Sizing Calculations 18. 19. ** Warning ** Since Zone Minimum Air Flow Input Method = CONSTANT, input for Fixed Minimum Air Flow Rate will be ignored. 20. 21. ** ~~~ ** Occurs in AirTerminal:SingleDuct:VAV:NoReheat = AIR TERMINAL SINGLE DUCT VAV NO REHEAT 1 22. 23. ** Warning ** Since Zone Minimum Air Flow Input Method = CONSTANT, input for Fixed Minimum Air Flow Rate will be ignored. 24. 25. ** ~~~ ** Occurs in AirTerminal:SingleDuct:VAV:NoReheat = AIR TERMINAL SINGLE DUCT VAV NO REHEAT 2 26. 27. ** Warning ** Since Zone Minimum Air Flow Input Method = CONSTANT, input for Fixed Minimum Air Flow Rate will be ignored. 28. 29. ** ~~~ ** Occurs in AirTerminal:SingleDuct:VAV:NoReheat = AIR TERMINAL SINGLE DUCT VAV NO REHEAT 10 30. 31. ** Warning ** Since Zone Minimum Air Flow Input Method = CONSTANT, input for Fixed Minimum Air Flow Rate will be ignored. 32. 33. ** ~~~ ** Occurs in AirTerminal:SingleDuct:VAV:NoReheat = AIR TERMINAL SINGLE DUCT VAV NO REHEAT 11 34. 35. ** Warning ** Since Zone Minimum Air Flow Input Method = CONSTANT, input for Fixed Minimum Air Flow Rate will be ignored. 36. 37. ** ~~~ ** Occurs in AirTerminal:SingleDuct:VAV:NoReheat = AIR TERMINAL SINGLE DUCT VAV NO REHEAT 12 38. 39. ** Warning ** Since Zone Minimum Air Flow Input Method = CONSTANT, input for Fixed Minimum Air Flow Rate will be ignored. 40. 41. ** ~~~ ** Occurs in AirTerminal:SingleDuct:VAV:NoReheat = AIR TERMINAL SINGLE DUCT VAV NO REHEAT 13 42. 43. ** Warning ** Since Zone Minimum Air Flow Input Method = CONSTANT, input for Fixed Minimum Air Flow Rate will be ignored. 44. 45. ** ~~~ ** Occurs in AirTerminal:SingleDuct:VAV:NoReheat = AIR TERMINAL SINGLE DUCT VAV NO REHEAT 14 46. 47. ** Warning ** Since Zone Minimum Air Flow Input Method = CONSTANT, input for Fixed Minimum Air Flow Rate will be ignored. 48. 49. ** ~~~ ** Occurs in AirTerminal:SingleDuct:VAV:NoReheat = AIR TERMINAL SINGLE DUCT VAV NO REHEAT 15 50. 51. ** Warning ** Since Zone Minimum Air Flow Input Method = CONSTANT, input for Fixed Minimum Air Flow Rate will be ignored. 52. 53. ** ~~~ ** Occurs in AirTerminal:SingleDuct:VAV:NoReheat = AIR TERMINAL SINGLE DUCT VAV NO REHEAT 16 54. 55. ** Warning ** Since Zone Minimum Air Flow Input Method = CONSTANT, input for Fixed Minimum Air Flow Rate will be ignored. 56. 57. ** ~~~ ** Occurs in AirTerminal:SingleDuct:VAV:NoReheat = AIR TERMINAL SINGLE DUCT VAV NO REHEAT 3 58. 59. ** Warning ** Since Zone Minimum Air Flow Input Method = CONSTANT, input for Fixed Minimum Air Flow Rate will be ignored. 60. 61. ** ~~~ ** Occurs in AirTerminal:SingleDuct:VAV:NoReheat = AIR TERMINAL SINGLE DUCT VAV NO REHEAT 4 62. 63. ** Warning ** Since Zone Minimum Air Flow Input Method = CONSTANT, input for Fixed Minimum Air Flow Rate will be ignored. 64. 65. ** ~~~ ** Occurs in AirTerminal:SingleDuct:VAV:NoReheat = AIR TERMINAL SINGLE DUCT VAV NO REHEAT 5 66. 67. ** Warning ** Since Zone Minimum Air Flow Input Method = CONSTANT, input for Fixed Minimum Air Flow Rate will be ignored. 68. 69. ** ~~~ ** Occurs in AirTerminal:SingleDuct:VAV:NoReheat = AIR TERMINAL SINGLE DUCT VAV NO REHEAT 6 70. 71. ** Warning ** Since Zone Minimum Air Flow Input Method = CONSTANT, input for Fixed Minimum Air Flow Rate will be ignored. 72. 73. ** ~~~ ** Occurs in AirTerminal:SingleDuct:VAV:NoReheat = AIR TERMINAL SINGLE DUCT VAV NO REHEAT 7 74. 75. ** Warning ** Since Zone Minimum Air Flow Input Method = CONSTANT, input for Fixed Minimum Air Flow Rate will be ignored. 76. 77. ** ~~~ ** Occurs in AirTerminal:SingleDuct:VAV:NoReheat = AIR TERMINAL SINGLE DUCT VAV NO REHEAT 8 78. 79. ** Warning ** Since Zone Minimum Air Flow Input Method = CONSTANT, input for Fixed Minimum Air Flow Rate will be ignored. 80. 81. ** ~~~ ** Occurs in AirTerminal:SingleDuct:VAV:NoReheat = AIR TERMINAL SINGLE DUCT VAV NO REHEAT 9 82. 83. ** Warning ** HVACControllers: GetControllerInput: Controller:WaterCoil="CONTROLLER WATER COIL 2". 84. 85. ** ~~~ ** ..Sensor node not found on water coil air outlet node. 86. 87. ** ~~~ ** ..The sensor node may have been placed on a node downstream of the coil or on an airloop outlet node. 88. 89. ** Severe ** CheckControllerListOrder: A water coil controller list has the wrong order 90. 91. ** ~~~ ** Check the AirLoopHVAC:ControllerList for the air loop called "DOAS AIR LOOP HVAC1" 92. 93. ** ~~~ ** When there are multiple Controller:WaterCoil objects for the same air loop, they need to be listed in the proper order. 94. 95. ** ~~~ ** The controllers should be listed in natural flow order with those for upstream coils listed before those for downstream coils. 96. 97. ** ~~~ ** The sensed nodes specified for the respective controllers should also reflect this order. 98. 99. ************* Beginning Plant Sizing Calculations 100. 101. ** Warning ** In calculating the design coil UA for Coil:Cooling:Water COIL COOLING WATER 1 102. 103. ** ~~~ ** no apparatus dew-point can be found for the initial entering and leaving conditions; 104. 105. ** ~~~ ** the coil outlet design conditions will be changed to correct the problem. 106. 107. ** ~~~ ** The initial design conditions are: Tair,in = 35.8890 108. 109. ** ~~~ ** Wair,in = 2.026342E-002 110. 111. ** ~~~ ** Twater,in = 6.6667 112. 113. ** ~~~ ** Tair,out = 12.8000 114. 115. ** ~~~ ** Wair,out = 8.275850E-003 116. 117. ** ~~~ ** The revised design conditions are: Tair,out = 12.7997 118. 119. ** ~~~ ** Wair,out = 8.275954E-003 120. 121. ** Warning ** GetElectricEIRChillerInput: Chiller:Electric:EIR="CHILLER ELECTRIC EIR 1" 122. 123. ** ~~~ ** Adding OutdoorAir:Node=CHILLER ELECTRIC EIR 1 INLET NODE FOR CONDENSER 124. 125. ** Warning ** GetElectricEIRChillerInput: Chiller:Electric:EIR="CHILLER ELECTRIC EIR 1" 126. 127. ** ~~~ ** Energy input ratio as a function of temperature curve output is not equal to 1.0 (+ or - 10%) at reference conditions. 128. 129. ** ~~~ ** Curve output at reference conditions = 0.852 130. 131. ************* Testing Individual Branch Integrity 132. 133. ************* All Branches passed integrity testing 134. 135. ************* Testing Individual Supply Air Path Integrity 136. 137. ************* All Supply Air Paths passed integrity testing 138. 139. ************* Testing Individual Return Air Path Integrity 140. 141. ************* All Return Air Paths passed integrity testing 142. 143. ************* No node connection errors were found. 144. 145. ************* Beginning Simulation 146. 147. ** Warning ** HeatExchanger:AirToAir:SensibleAndLatent "HEAT EXCHANGER AIR TO AIR SENSIBLE AND LATENT 1" 148. 149. ** ~~~ ** Average air volume flow rate is <50% or >130% of the nominal HX supply air volume flow rate. 150. 151. ** ~~~ ** Air volume flow rate ratio = 0.299. Environment=RUN PERIOD 1, at Simulation time=01/01 00:00 - 00:10 152. 153. ** Warning ** Calculated Relative Humidity out of range (PsyRhFnTdbWPb) 154. 155. ** ~~~ ** Routine=NodeReportingCalc:NODE 59, Environment=RUN PERIOD 1, at Simulation time=01/14 12:20 - 12:30 156. 157. ** ~~~ ** Dry-Bulb= 6.71 Humidity Ratio= 6.171E-003 Calculated Relative Humidity [%]= 101.16 158. 159. ** ~~~ ** Relative Humidity being reset to 100.0% 160. 161. ************* Simulation Error Summary ************* 162. 163. ** Warning ** The following Report Variables were requested but not generated 164. 165. ** ~~~ ** because IDF did not contain these elements or misspelled variable name -- check .rdd file 166. 167. ************* Key=*, VarName=ZONE IDEAL LOADS SUPPLY AIR TOTAL COOLING ENERGY, Frequency=Hourly 168. 169. ************* Key=*, VarName=EARTH TUBE FAN ELECTRIC ENERGY, Frequency=Hourly 170. 171. ************* Key=*, VarName=ZONE VRF AIR TERMINAL COOLING ELECTRIC ENERGY, Frequency=Hourly 172. 173. ************* Key=*, VarName=ZONE VRF AIR TERMINAL HEATING ELECTRIC ENERGY, Frequency=Hourly 174. 175. ************* Key=*, VarName=VRF HEAT PUMP COOLING ELECTRIC ENERGY, Frequency=Hourly 176. 177. ************* Key=*, VarName=VRF HEAT PUMP HEATING ELECTRIC ENERGY, Frequency=Hourly 178. 179. ************* Key=*, VarName=ZONE IDEAL LOADS SUPPLY AIR TOTAL HEATING ENERGY, Frequency=Hourly 180. 181. ************* Key=*, VarName=ZONE IDEAL LOADS ZONE TOTAL HEATING ENERGY, Frequency=Hourly 182. 183. ************* Key=*, VarName=ZONE IDEAL LOADS ZONE TOTAL COOLING ENERGY, Frequency=Hourly 184. 185. ************* Key=*, VarName=COOLING COIL ELECTRIC ENERGY, Frequency=Hourly 186. 187. ************* Key=*, VarName=HEATING COIL TOTAL HEATING ENERGY, Frequency=Hourly 188. 189. ************* Key=*, VarName=HEATING COIL GAS ENERGY, Frequency=Hourly 190. 191. ************* Key=*, VarName=HEATING COIL ELECTRIC ENERGY, Frequency=Hourly 192. 193. ************* There are 2 unused schedules in input. 194. 195. ************* There are 2 unused week schedules in input. 196. 197. ************* There are 2 unused day schedules in input. 198. 199. ************* Use Output:Diagnostics,DisplayUnusedSchedules; to see them. 200. 201. ************* 202. 203. ************* ===== Recurring Error Summary ===== 204. 205. ************* The following recurring error messages occurred. 206. 207. ************* 208. 209. ************* ** Warning ** HeatExchanger:AirToAir:SensibleAndLatent "HEAT EXCHANGER AIR TO AIR SENSIBLE AND LATENT 1": Average air volume flow rate is <50% or >130% warning continues. Air flow rate ratio statistics follow. 210. 211. ************* ** ~~~ ** This error occurred 1117883 total times; 212. 213. ************* ** ~~~ ** during Warmup 0 times; 214. 215. ************* ** ~~~ ** during Sizing 0 times. 216. 217. ************* ** ~~~ ** Max=0.302084 Min=0.299244 218. 219. ************* 220. 221. ************* ** Warning ** Calculated Relative Humidity out of range (PsyRhFnTdbWPb) 222. 223. ************* ** ~~~ ** This error occurred 53 total times; 224. 225. ************* ** ~~~ ** during Warmup 0 times; 226. 227. ************* ** ~~~ ** during Sizing 0 times. 228. 229. ************* ** ~~~ ** Max=102.123719 % Min=101.112368 % 230. 231. ************* 232. 233. ************* 234. 235. ************* ===== Final Error Summary ===== 236. 237. ************* The following error categories occurred. Consider correcting or noting. 238. 239. ************* InterZone Surface Areas -- mismatch 240. 241. ************* ..Area mismatch errors happen when the interzone surface in zone A is 242. 243. ************* ..not the same size as it's companion in zone B. 244. 245. ************* 246. 247. ************* EnergyPlus Warmup Error Summary. During Warmup: 0 Warning; 0 Severe Errors. 248. 249. ************* EnergyPlus Sizing Error Summary. During Sizing: 19 Warning; 1 Severe Errors. 250. 251. ************* EnergyPlus Completed Successfully-- 1117960 Warning; 1 Severe Errors; Elapsed Time=00hr 01min 14.61sec 252.